10-21 COS Filter 2
Range:
Function:
0*
[0 - 65535 ]
Enter the value for COS Filter 2, to set up the filter mask for the Main Actual Value. When operating
in COS (Change-Of-State), this function filters out bits in the Main Actual Value that should not be
sent if they change.
10-22 COS Filter 3
Range:
Function:
0*
[0 - 65535 ]
Enter the value for COS Filter 3, to set up the filter mask for PCD 3. When operating in COS (Change-
Of-State), this function filters out bits in PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range:
Function:
0*
[0 - 65535 ]
Enter the value for COS Filter 4 to set up the filter mask for PCD 4. When operating in COS (Change-
Of-State), this function filters out bits in PCD 4 that should not be sent if they change.
2.11.5 10-3* Parameter Access
Parameter group providing access to indexed parameters and defining programming set-up.
10-30 Array Index
Range:
Function:
0*
[0 - 255 ]
View array parameters. This parameter is valid only when a DeviceNet fieldbus is installed.
10-31 Store Data Values
Option:
Function:
Parameter values changed via DeviceNet are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
[0] *
Off
Deactivates the non-volatile storage function.
[1]
Store edit setup
Stores all parameter values from the active set-up in the non-volatile memory. The selection returns
to Off [0] when all values have been stored.
[2]
Store all setups
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
10-32 Devicenet Revision
Range:
Function:
Application
dependent*
[0 - 65535 ]
View the DeviceNet revision number. This parameter is used for EDS file creation.
10-33 Store Always
Option:
Function:
[0] *
Off
Deactivates non-volatile storage of data.
[1]
On
Stores parameter data received via DeviceNet in EEPROM non-volatile memory as default.