2.13 Main Menu - Frequency Converter Information - Group 15
2.14.1 15-** Drive Information
Parameter group containing frequency converter information such as operating data, hardware configuration and software versions.
2.14.2 15-0* Operating Data
Parameter group containing operating data e.g. Operating Hours, kWh counters, Power Ups, etc.
15-00 Operating Hours
Range:
Function:
0 h*
[0 - 2147483647 h]
View how many hours the frequency converter has run. The value is saved when the frequency
converter is turned off.
15-01 Running Hours
Range:
Function:
0 h*
[0 - 2147483647 h]
View how many hours the motor has run. Reset the counter in par. 15-07
Reset Running Hours
Counter
. The value is saved when the frequency converter is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh*
[0 - 2147483647 kWh]
Registering the power consumption of the motor as a mean value over one hour. Reset the counter
in par. 15-06
Reset kWh Counter
.
15-03 Power Up's
Range:
Function:
0*
[0 - 2147483647 ]
View the number of times the frequency converter has been powered up.
15-04 Over Temp's
Range:
Function:
0*
[0 - 65535 ]
View the number of frequency converter temperature faults which have occurred.
15-05 Over Volt's
Range:
Function:
0*
[0 - 65535 ]
View the number of frequency converter overvoltages which have occurred.
15-06 Reset kWh Counter
Option:
Function:
[0] *
Do not reset
Select
Do not reset
[0] if no reset of the kWh counter is desired.
[1]
Reset counter
Select
Reset
[1] and press [OK] to reset the kWh counter to zero (see par. 15-02
kWh Counter
).
NB!
The reset is carried out by pressing [OK].
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
166
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
2