1-39 Motor Poles
Range:
Function:
Application
dependent*
[2 - 100 ]
Enter the number of motor poles.
Poles
~n
n
@ 50 Hz
~n
n
@60 Hz
2
2700 - 2880
3250 - 3460
4
1350 - 1450
1625 - 1730
6
700 - 960
840 - 1153
The table shows the number of poles for normal speed ranges of various motor types. Define motors
designed for other frequencies separately. The motor pole value is always an even number, because
it refers to the total number of poles, not pairs of poles. The frequency converter creates the initial
setting of par. 1-39
Motor Poles
based on par. 1-23
Motor Frequency
Motor Frequency
and
par. 1-25
Motor Nominal Speed
Motor Nominal Speed
.
This parameter cannot be adjusted while the motor is running.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description