0-11 Programming Set-up
Option:
Function:
Select the set-up to be edited (i.e. programmed) during operation; either the active set-up or one
of the inactive set-ups. The set-up number being edited is displayed in the LCP in (brackets).
[0]
Factory setup
cannot be edited but it is useful as a data source to return the other set-ups to a known state.
[1]
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited freely during operation, independently of the active set-
up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9] *
Active Set-up
(i.e. the set-up in which the frequency converter is operating) can also be edited during operation.
Editing parameters in the chosen setup would normally be done from the LCP but it is also possible
from any of the serial communication ports.
0-12 This Set-up Linked to
Option:
Function:
This parameter only needs to be programmed if changing set-ups is required whilst the motor is
running. It ensures that parameters which are "not changeable during operation" have the same
setting in all relevant set-ups.
To enable conflict-free changes from one set-up to another whilst the frequency converter is run-
ning, link set-ups containing parameters which are not changeable during operation. The link will
ensure synchronising of the ‘not changeable during operation’ parameter values when moving from
one set-up to another during operation. ‘Not changeable during operation’ parameters can be iden-
tified by the label FALSE in the parameter lists in the section
Parameter Lists
.
The par. 0-12
This Set-up Linked to
feature is used when Multi set-up in par. 0-10
Active Set-up
is
selected. Multi set-up can be used to move from one set-up to another during operation (i.e. while
the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 whilst the motor is running. Programme param-
eters in Set-up 1 first, then ensure that Set-up 1 and Set-up 2 are synchronised (or ‘linked’). Syn-
chronisation can be performed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in par. 0-11
Programming Set-up
and set par. 0-12
This
Set-up Linked to
to
Set-up 1
[1]. This will start the linking (synchronising) process.
OR
2. While still in Set-up 1, using par. 0-50
LCP Copy
, copy Set-up 1 to Set-up 2. Then set
par. 0-12
This Set-up Linked to
to
Set-up 2
[2]. This will start the linking process.