14-52 Fan Control
Option:
Function:
Select the minimum speed of the main fan.
[0] *
Auto
Select Auto [0] to run the fan only when the internal temperature of the frequency converter is in
the range +35
r
C to approxi55
r
C. The fan will run at low speed at +35
r
C and at full speed
at approxi55
r
C.
[1]
On 50%
[2]
On 75%
[3]
On 100%
[4]
Auto (Low temp env.)
14-53 Fan Monitor
Option:
Function:
Select which reaction the frequency converter should take in case a fan fault is detected.
[0]
Disabled
[1] *
Warning
[2]
Trip
14-53 Fan Monitor
Option:
Function:
Select which reaction the frequency converter should take in case a fan fault is detected.
[0]
Disabled
[1] *
Warning
[2]
Trip
2.13.8 14-6* Auto Derate
This group contains parameters for derating the frequency converter in case of high temperature.
14-60 Function at Overtemperature
Option:
Function:
[0]
Trip
[1] *
Derate
If either heatsink or control card temperature exceeds a programmed temperature limit, a warning
will be activated. If the temperature increases further, select whether the frequency converter
should trip (trip locked) or derate the output current.
Trip
[0]: The frequency converter will trip (trip locked) and generate an alarm. Power must be cycled
to reset the alarm, but will not allow restart of the motor until the heat sink temperature has dropped
below the alarm limit.
Derate
[1]: If the critical temperature is exceeded the output current will be reduced until the al-
lowable temperature has been reached.