2.7 Main Menu - Analog In/Out - Group 6
2.8.1 6-** Analog In/Out
Parameter group for configuration of the analog input and output.
2.8.2 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can freely be allocated to either voltage (0 - 10 V) or
current input (0/4 - 20 mA)
NB!
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range:
Function:
10 s*
[1 - 99 s]
Enter the Live Zero Time-out time period. Live Zero Time-out Time is active for analog inputs, i.e.
terminal 53 or terminal 54, used as reference or feedback sources. If the reference signal value
associated with the selected current input falls below 50% of the value set in par. 6-10
Terminal 53
Low Voltage
, par. 6-12
Terminal 53 Low Current
, par. 6-20
Terminal 54 Low Voltage
or
par. 6-22
Terminal 54 Low Current
for a time period longer than the time set in par. 6-00
Live Zero
Timeout Time
, the function selected in par. 6-01
Live Zero Timeout Function
will be activated.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark