2.8 Main Menu - Communications and Options - Group 8
2.9.1 8-** Comm. and Options
Parameter group for configuring communications and options.
2.9.2 8-0* General Settings
General settings for communications and options.
8-01 Control Site
Option:
Function:
The setting in this parameter overrides the settings in par. 8-50
Coasting Select
to par. 8-56
Preset
Reference Select
.
[0] *
Digital and ctrl.word
Control by using both digital input and control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword only
Control by using control word only.
8-02 Control Word Source
Option:
Function:
Select the source of the control word: one of two serial interfaces or four installed options. During
initial power-up, the frequency converter automatically sets this parameter to
Option A
[3] if it
detects a valid fieldbus option installed in slot A. If the option is removed, the frequency converter
detects a change in the configuration, sets par. 8-02 back to default setting
FC Port
, and the fre-
quency converter then trips. If an option is installed after initial power-up, the setting of par. 8-02
will not change but the frequency converter will trip and display: Alarm 67
Option Changed
.
This parameter cannot be adjusted while the motor is running.
[0]
None
[1]
FC Port
[2]
FC USB
[3]
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
111
2