3 Product Overview
3.1 Intended Use
NOTICE
OUTPUT FREQUENCY LIMIT
Due to export control regulations, the output frequency of the drive is limited to 590 Hz. For demands exceeding 590 Hz,
contact Danfoss.
The drive is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency and
voltage of the output are regulated to control the motor speed or torque. The drive is designed to:
•
Regulate motor speed in response to system feedback or remote commands from external controllers.
•
Monitor system and motor status.
•
Provide motor overload protection.
Depending on the configuration, the drive can be used in standalone applications or form part of a larger system or installation.
The drive is allowed for use in industrial and commercial environments in accordance with local laws and standards. Do not use the
drive in applications which are non-compliant with specified operating conditions and environments.
3.2 Power Ratings, Weights, and Dimensions for E1h–E4h Enclosures
Table 2: Power Ratings, Weights, and Dimensions for E1h–E4h Enclosures (Standard Configurations)
Enclosure size
E1h
E2h
E3h
E4h
Rated power at 380–480 V [kW
(hp)]
355–450 (500–600)
500–560 (650–750)
355–450 (500–600)
500–560 (650–750)
Rated power at 525–690 V [kW
(hp)]
450–6300 (450–650)
710–800 (750–950)
450–630 (450–650)
710–800 (750–950)
Enclosure protection rating
(1)
IP21/Type 1 IP54/
Type 12
IP21/Type 1 IP54/
Type 12
IP20/Chassis
IP20/Chassis
Unit dimensions
Height [mm (in)]
2043 (80.4)
2043 (80.4)
1578 (62.1)
1578 (62.1)
Width [mm (in)]
602 (23.7)
698 (27.5)
506 (19.9)
604 (23.89)
Depth [mm (in)]
513 (20.2)
513 (20.2)
482 (19.0)
482 (19.0)
Weight [kg (lb)]
295 (650)
318 (700)
272 (600)
295 (650)
Shipping dimensions
Height [mm (in)]
2191 (86.3)
2191 (86.3)
1759 (69.3)
1759 (69.3)
Width [mm (in)]
768 (30.2)
768 (30.2)
746 (29.4)
746 (29.4)
Depth [mm (in)]
870 (34.3)
870 (34.3)
794 (31.3)
794 (31.3)
Weight [kg (lb)]
–
–
–
–
1
Type 1 and Type 12 are UL designations.
Product Overview
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
12 | Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...