7 Wiring Configuration Examples
7.1 Application Examples
The examples in this section are intended as a quick reference for common applications.
•
Parameter settings are the regional default values unless otherwise indicated (selected in
parameter 0-03 Regional Settings
).
•
Parameters associated with the terminals and their settings are shown next to the drawings.
•
Required switch settings for analog terminals A53 or A54 are also shown.
7.1.1 Wiring Configuration for Automatic Motor Adaptation (AMA)
Table 16: Wiring Configuration for AMA with T27 Connected
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
e3
0b
b9
29
.1
1
Drive
Function
Setting
Parameter 1-29 Automatic Motor Adaptation (AMA)
[1] Enable complete AMA
Parameter 5-12 Terminal 27 Digital Input
[2]* Coast inverse
*=Default value
Notes/comments:
Set
parameter group 1-2* Motor Data
according to motor nameplate.
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
74 | Danfoss A/S © 2020.01