Troubleshooting
•
Remove the power to the drive and remove the brake resistor.
8.4.25 WARNING/ALARM 28, Brake Check Failed
Cause
The brake resistor is not connected or not working.
Troubleshooting
•
Check
parameter 2-15 Brake Check
.
8.4.26 ALARM 29, Heat Sink Temp
Cause
The maximum temperature of the heat sink is exceeded. The temperature fault is not reset until the temperature drops below a
defined heat sink temperature. The trip and reset points are different based on the drive power size.
Troubleshooting
•
The ambient temperature is too high.
•
The motor cables are too long.
•
Incorrect airflow clearance above and below the drive.
•
Blocked airflow around the drive.
•
Damaged heat sink fan.
•
Dirty heat sink.
8.4.27 ALARM 30, Motor Phase U Missing
Cause
Motor phase U between the drive and the motor is missing.
Troubleshooting
WARNING
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation,
start-up, and maintenance by qualified personnel can result in death or serious injury.
-
Only qualified personnel must perform installation, start-up, and maintenance.
•
Disconnect power before proceeding.
•
Remove the power from the drive and check motor phase U.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 111
Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...