Symptom
Possible cause
Test
Solution
Motor not run-
ning
Service switch open or miss-
ing motor connection.
–
Connect the motor and check the serv-
ice switch.
No mains power with 24 V DC
option card.
–
Apply mains power.
LCP stop.
–
Depending on the operating mode,
press [Auto On] or [Hand On].
Missing start signal (Standby).
–
Apply a valid start signal.
Motor coast signal active
(Coasting).
–
Apply 24 V on terminal 27 or program
this terminal to
[0] No operation
.
Wrong reference signal
source.
Check reference signal:
•
Local
•
Remote or bus reference?
•
Preset reference active?
•
Terminal connection correct?
•
Scaling of terminals correct?
•
Reference signal available?
Program correct settings. Check
param-
eter 3-13 Reference Site
. Set preset refer-
ence active in
parameter group 3-1* Ref-
erences
. Check for correct wiring. Check
scaling of terminals. Check reference
signal.
Motor running
in wrong direc-
tion
Motor rotation limit.
Check that
parameter 4-10 Motor
Speed Direction
is programmed
correctly.
Program correct settings.
Active reversing signal.
Check if a reversing command is
programmed for the terminal in
parameter group 5-1* Digital inputs
.
Deactivate reversing signal.
Wrong motor phase connec-
tion.
–
Correct motor phase connection, or set
parameter 1-06 Clockwise Direction
to
[1]
Inverse
.
Motor is not
reaching maxi-
mum speed
Frequency limits set wrong.
Check output limits in
parameter
4-13 Motor Speed High Limit [RPM]
,
parameter 4-14 Motor Speed High
Limit [Hz]
, and
parameter 4-19 Max
Output Frequency
.
Program correct limits.
Reference input signal not
scaled correctly.
Check reference input signal scal-
ing in
parameter group 6-0* Analog
I/O mode
and
parameter group 3-1*
References
.
Program correct settings.
Motor speed
unstable
Possible incorrect parameter
settings.
Check the settings of all motor pa-
rameters, including all motor com-
pensation settings. For closed-loop
operation, check PID settings.
Check settings in
parameter group 1-6*
Load Depen. Setting
. For closed-loop
operation, check settings in
parameter
group 20-0* Feedback
.
Motor runs
rough
Possible overmagnetization.
Check for incorrect motor settings
in all motor parameters.
Check motor settings in
parameter
groups 1-2* Motor data
,
1-3* Adv Motor
Data
, and
1-5* Load Indep. Setting
.
Motor does not
brake
Possible incorrect settings in
the brake parameters. Ramp-
down times may be too short.
Check brake parameters. Check
ramp time settings.
Check
parameter groups 2-0* DC Brake
and
3-0* Reference Limits
.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
128 | Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...