6.6.3 Restoring Factory Default Settings Using the Recommended Initialization
Context:
NOTICE
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
-
To create a back-up, upload data to the LCP before initialization. See
6.6.2 Uploading and Downloading Parameter Settings
1. Press [Main Menu] twice to access parameters.
2. Go to
parameter 14-22 Operation Mode
and press [OK].
Parameter 14-22 Operation Mode
does not reset the following settings:
•
Running hours.
•
Serial communication options.
•
Personal menu settings.
•
Fault log, alarm log, and other monitoring functions.
3. Scroll to Initialization and press [OK].
4. Remove power to the unit and wait for the display to turn off.
5. Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal.
6. After
alarm 80, Drive initialized
appears, press [Reset].
6.6.4 Restoring Factory Default Settings Using Manual Initialization
Context:
NOTICE
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
-
To create a back-up, upload data to the LCP before initialization. See
6.6.2 Uploading and Downloading Parameter Settings
Procedure
1. Remove power to the unit and wait for the display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until an
audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
•
Parameter 15-00 Operating Hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
Start-up takes slightly longer than normal.
Starting the Drive
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 73
Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...