Troubleshooting
•
Check for motor overheating.
•
Check if the motor is mechanically overloaded.
•
Check that the motor current set in
parameter 1-24 Motor Current
is correct.
•
Ensure that the motor data in
parameters 1-20
to
1-25
is set correctly.
•
If an external fan is in use, check that it is selected in
parameter 1-91 Motor External Fan
.
•
Running AMA in
parameter 1-29 Automatic Motor Adaptation (AMA)
tunes the drive to the motor more accurately and reduces
thermal loading.
8.4.11 WARNING/ALARM 11, Motor Thermistor Overtemp
The motor thermistor indicates that the motor temperature is too high.
Troubleshooting
•
Check for motor overheating.
•
Check that the thermistor is securely connected.
•
Check if the motor is mechanically overloaded.
•
When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage
input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 and 54 is set for voltage. Check that
parameter 1-93
Thermistor Resource
selects 53 or 54.
•
When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input
terminal used (digital input PNP only) and terminal 50. Select the terminal to use in
parameter 1-93 Thermistor Resource
.
8.4.12 WARNING/ALARM 12, Torque Limit
Cause
The torque has exceeded the value in
parameter 4-16 Torque Limit Motor Mode
or the value in
parameter 4-17 Torque Limit Generator
Mode
.
Parameter 14-25 Trip Delay at Torque Limit
can change this warning from a warning-only condition to a warning followed by an
alarm.
Troubleshooting
•
If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
•
If the generator torque limit is exceeded during ramp-down time, extend the ramp-down time.
•
If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque.
•
Check the application for excessive current draw on the motor.
8.4.13 ALARM 14, Earth (Ground) Fault
Cause
There is current from the output phase to ground, either in the cable between the drive and the motor, or in the motor itself. The
current transducers detect the ground fault by measuring current going out from the drive and current going into the drive from the
motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the drive must be the same as the
current going into the drive.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 107
Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...