4.4.3 Dust
When installing the unit in a dusty environment, keep the following free from dust buildup:
•
Electronic components.
•
Heat sink.
•
Fans.
Keep the heat sink and fans free from dust buildup. When dust accumulates on electronic components, it acts as a layer of insulation.
This layer reduces the cooling capacity of the components, and the components become warmer. The hotter environment decreases
the life of the electronic components. Dust can also accumulate on fan blades, causing an imbalance which prevents the fan from
properly cooling the unit. Dust buildup can also damage fan bearings and cause premature fan failure.
For more information, refer to the
Maintenance and Service
section.
4.4.4 Potentially Explosive Atmospheres
WARNING
EXPLOSIVE ATMOSPHERE
Installing the drive in a potentially explosive atmosphere can lead to death, personal injury, or property damage.
-
Install the unit in a cabinet outside of the potentially explosive area.
-
Use a motor with an appropriate ATEX protection class.
-
Install a PTC temperature sensor to monitor the motor temperature.
-
Install short motor cables.
-
Use sine-wave output filters when shielded motor cables are not used.
As required by the EU Directive 2014/34/EU, any electrical or electronic device intended for use in an environment with a potentially
explosive mixture of air, flammable gas, or dust must be ATEX-certified. Systems operated in this environment must fulfill the following
special conditions to comply with the ATEX protection class:
•
Class d specifies that if a spark occurs, it is contained in a protected area.
•
Class e prohibits any occurrence of a spark.
Motors with class d protection
Does not require approval. Special wiring and containment are required.
Motors with class e or class n protection
When combined with an ATEX-approved PTC monitoring device like the VLT
®
PTC Thermistor Card MCB 112, installation does not need
an individual approval from an approbated organization.
Motors with class d/e protection
The motor itself has an e ignition protection class, while the motor cabling and connection environment are in compliance with the d
classification. To attenuate the high peak voltage, use a sine-wave filter at the drive output.
Mechanical Installation
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
24 | Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...