7.1.4 Wiring Configuration: Feedback
Table 22: Analog Current Feedback Transducer (2-wire)
Parameters
4-20 mA
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A 54
U - I
+
-
e3
0b
b6
75
.1
1
Drive
Function
Setting
Parameter 6-22 Terminal 54 Low Current
4 mA*
Parameter 6-23 Terminal 54 High Current
20 mA*
Parameter 6-24 Terminal 54 Low Ref./Feedb. value
0*
Parameter 6-25 Terminal 54 High Ref./Feedb. Value
50*
*=Default value
Notes/comments:
D IN 37 is an option.
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
78 | Danfoss A/S © 2020.01