RELAY 1
RELAY 2
01 02 03
04 05 06
e
3
0
b
f1
5
6
.1
0
Illustration 35: Relay 1 and Relay 2 Terminals
Table 13: Relay Terminal Descriptions
Terminal
Parameter
Default setting
Description
01, 02, 03
Parameter 5-40 Function Relay [0]
[0] No operation
Form C relay output. For AC or DC voltage and resistive or in-
ductive loads.
04, 05, 06
Parameter 5-40 Function Relay [1]
[0] No operation
5.11.5 Connecting the Control Cable to the Control Terminals
Context:
The control terminals are located near the LCP. The control terminal connectors can be unplugged from the drive for convenience
when wiring, as shown in
. Either solid or flexible wire can be connected to the control terminals. For minimum and
maximum control cable cross-section, refer to
NOTICE
ELECTRICAL INTERFERENCE
Minimize interference by keeping control wires as short as possible and separate from high-power cables.
Procedure
1. Strip 10 mm (0.4 in) of the outer plastic layer from the end of the wire.
2. Insert the control wire into the terminal.
For a solid wire, push the bare wire into the contact.
For a flexible wire, open the contact by inserting a small screwdriver into the slot between the terminal holes and push the
screwdriver inward. Then insert the stripped wire into the contact, and remove the screwdriver.
3. Pull gently on the wire to ensure that the contact is firmly established.
Loose control cable can cause equipment faults or reduced performance.
Electrical Installation
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
60 | Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...