Troubleshooting
•
Check wiring.
•
Check the on-board temperature sensor.
•
Replace fan power card.
8.4.96 ALARM 423, FPC Updating
Cause
The alarm is generated when the fan power card reports it has an invalid PUD. The control card attempts to update the PUD. A
subsequent alarm can result depending on the update. See
Alarm 424, FPC Update Successful
and
Alarm 425 FPC Update Failure
.
8.4.97 ALARM 424, FPC Update Successful
Cause
This alarm is generated when the control card has successfully updated the fan power card PUD.
Troubleshooting
•
Press [Reset] to stop the alarm.
8.4.98 ALARM 425, FPC Update Failure
Cause
This alarm is generated after the control card failed to update the fan power card PUD.
Troubleshooting
•
Check the fan power card wiring.
•
Replace fan power card.
•
Contact supplier.
8.4.99 ALARM 426, FPC Config
Cause
The number of found fan power cards does not match the number of configured fan power cards. See
parameter group 15-6* Option
Ident
for the number of configured fan power cards.
Troubleshooting
•
Check fan power card wiring.
•
Replace fan power card.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
126 | Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...