Table 19: Analog Speed Reference (Current)
Parameters
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
e3
0b
b9
27
.1
1
A53
U - I
4-20mA
Drive
Function
Setting
Parameter 6-12 Terminal 53 Low Current
4 mA*
Parameter 6-13 Terminal 53 High Current
20 mA*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Table 20: Speed Reference (Using a Manual Potentiometer)
Parameters
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
≈
5k
Ω
e3
0b
b6
83
.1
1
Drive
Function
Setting
Parameter 6-10 Terminal 53 Low Voltage
0.07 V*
Parameter 6-11 Terminal 53 High Voltage
10 V*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
76 | Danfoss A/S © 2020.01