FC 202
N450
N500
N560
Continuous (at 575/690 V) [A]
380
450
410
500
500
570
Intermittent (60 s overload) (at 575/690 V) [A]
570
495
615
550
750
627
Continuous kVA (at 525 V) [kVA]
359
427
390
476
476
542
Continuous kVA (at 575 V) [kVA]
378
448
408
498
498
568
Continuous kVA (at 690 V) [kVA]
454
538
490
598
598
681
Maximum input current
Continuous (at 525 V) [A]
381
453
413
504
504
574
Continuous (at 575/690 V) [A]
366
434
395
482
482
549
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
2
(AWG)]
5x240 (5x500 mcm)
5x240 (5x500 mcm)
5x240 (5x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
(1)
800
800
800
Estimated power loss at 600 V [W]
(2) (3)
4763
5758
5164
6516
6480
7629
Estimated power loss at 690 V [W]
(2) (3)
4917
5935
5329
6711
6673
7846
Efficiency
(3)
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
1
.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3
. For part load losses, see www.danfoss.com/vltenergyefficiency.
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 133
Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...