7.1.10 Wiring for Regen
Table 34: Regen
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
e3
0b
d6
67
.1
1
Drive
Function
Setting
Parameter 1-90 Motor Thermal Protection
100%*
* = Default value
To disable regen, decrease
parameter 1-90 Motor Thermal Protection
to 0%. If the application uses
motor brake power and regen is not enabled, the unit trips.
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
90 | Danfoss A/S © 2020.01