FC 202
N500
N560
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E4h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
(1)
1200
1200
Estimated power loss at 400 V [W]
(2) (3)
8352
9473
9449
11102
Estimated power loss at 460 V [W]
(2) (3)
7182
7809
7771
9236
Efficiency
(3)
0.98
0.98
Output frequency [Hz]
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
100 (212)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
Power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
Fan power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
Active in-rush card overtemperature trip [°C (°F)]
85 (185)
85 (185)
1
.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3
. For part load losses, see www.danfoss.com/vltenergyefficiency.
9.1.2 Electrical Data, 525–690 V AC
Table 47: Electrical Data, Mains Supply 3x525–690 V AC
FC 202
N450
N500
N560
High/normal overload
High overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
HO
NO
HO
NO
HO
NO
Typical shaft output at 525 V [kW]
315
355
355
400
400
450
Typical shaft output at 575 V [hp]
400
450
400
500
500
600
Typical shaft output at 690 V [kW]
355
450
400
500
500
560
Enclosure size
E1h/E3h
E1h/E3h
E1h/E3h
Output current (3-phase)
Continuous (at 525 V) [A]
395
470
429
523
523
596
Intermittent (60 s overload) (at 525 V) [A]
593
517
644
575
785
656
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
132 | Danfoss A/S © 2020.01
Содержание VLT AQUA Drive FC 202
Страница 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Страница 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...