9.5.4
Execute spool auto-calibration from the PLUS+1 SERVICE TOOL
In the system navigator pane, find “Parameter pages”
“Auto-Calibration”
“Spool Calibration”
Figure 36
Press “Goto Spool Calibration Mode”.
Important
Before pressing the “
Start spool calibration
”-button, the steering has to be activated otherwise it will not engage the spool
calibration. See description for P3801 in section 9.4.1.1
Important
The wheels of the machine need to be in a straight-ahead position (within value for Spool calibration - +/- turn range
sweep; P3804), in order to start the spool auto-calibration routine.
Now the spool calibration can be started with the values stored in the EEPROM (P3797 – P3811), simply by pressing the
“Start spool calibration” button.