Troubleshooting for Wall Mounted and LSP Duct Type Indoor Unit
SiSG121917E
123
Part 6 Service Diagnosis
Reference
5.4 Thermistor or Related Abnormality (Indoor Unit)
Error Code
C4
,
C9
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
with the power on.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Defective indoor unit PCB
Troubleshooting
C4
: Indoor heat exchanger thermistor
C9
: Room temperature thermistor
Check No.01
Refer to P.169
YES
(R21
8
70)
N
O
Check No. 01
Check the thermistor resistance
v
al
u
e.
YES
N
O
Caution
Correct the connection.
Replace the defecti
v
e
thermistor.
Replace the indoor
u
nit PCB
(control PCB).
N
ormal?
N
ormal?
Check the connection of
connectors.
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...