Troubleshooting for MSP Duct Type Indoor Unit
Part 6 Service Diagnosis
134
Note
6.7 Remote Controller Thermistor Abnormality
Error Code
CJ
Method of Error
Detection
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by the remote controller
thermistor.
Error Decision
Conditions
The remote controller thermistor is disconnected or shorted while the unit is running.
Supposed
Causes
Defective thermistor
Broken wire
Troubleshooting
To delete the record of error codes, press
ON/OFF
button for 4 seconds or more while the error
code is displayed in the inspection mode.
Replace the remote
controller.
External factor other than
e
qu
ipment malf
u
nction.
(for example, noise etc.)
N
O
YES
(R21111)
Is
CJ
displayed on the
remote controller
again?
Delete the record of error
codes.
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.