Part 4 Functions and Control
82
4.6 Freeze-up Protection Control
4.6.1 Freeze-up Protection Control for Wall Mounted and LSP Duct Type
Outline
During cooling operation, the signals sent from the indoor unit control the operating frequency
limitation and prevent freezing of the indoor heat exchanger. The signal from the indoor unit is
divided into zones.
Details
The operating frequency limitation is judged with the indoor heat exchanger temperature 2
seconds after operation starts and 30 seconds after the number of operation room is changed.
4.6.2 Freeze-up Protection Control for MSP Duct Type
Outline
During cooling operation, the signal sent from the indoor unit determines the frequency upper
limit and prevents the indoor heat exchanger from freezing.
Details
When the freeze-up protection control starts, the compressor stops, the airflow rate is fixed to L
tap, and the drain pump turns ON. Conditions for starting and ending are as below.
Starting conditions
The freeze-up protection control starts when any of the following conditions is satisfied.
The indoor heat exchanger temperature remains at
A
°C or lower for 1 minute.
The accumulated time that the indoor heat exchanger temperature remains at
B
°C or lower
reaches 40 minutes.
Accumulated timer clearing condition
The indoor heat exchanger temperature remains at
C
°C or higher for 20 minutes.
Ending condition
The indoor heat exchanger temperature remains at
D
°C or higher for 10 minutes.
R4003618
A
(°C)
B
(°C)
C
(°C)
11
10.5
10
(R23581)
Reset zone
Indoor heat exchanger
temperature
Up zone
Keep zone
Dropping zone
Stop zone
0˚C
C
˚C
B
˚C
A
˚C
13˚C
A
(°C)
B
(°C)
C
(°C)
D
(°C)
–5
–1
4
7
D
(°C)
A
(°C)
B
(°C)
C
(°C)
Indoor heat
exchanger
temperature
The control starts.
The control starts.
The control ends
and the accumulated timer is cleared.
The accumulated timer is cleared.
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...