Trial Operation
SiSG121917E
189
Part 7 Trial Operation and Field Settings
Test Items
* For wireless LAN connecting adapter, please check the FAQ at
http://www.daikinthai.com/product/dmobile
4.2 Outdoor Unit
During the trial operation, first check the operation of each unit individually. After this, check
the simultaneous operation of all indoor units. Check COOL operation.
Measure the supply voltage and make sure that it is within the specified range.
In COOL operation, select the lowest programmable temperature.
Carry out the trial operation following the instructions in the operation manual to
ensure that all functions and parts, such as the movement of the flap, are working
properly.
To protect the air conditioner, restart operation is disabled for 3 minutes after the system
has been turned off.
During COOL operation, frost may form on the gas stop valve or other parts. This is
normal.
After running the unit for about 20 minutes, measure the temperatures at the indoor
unit inlet and outlet.
If the measurements are above the values shown in the table below, then they are
normal.
(When running in one room)
After trial operation is complete, set the temperature to a normal level (26°C to 28°C).
When operating the air conditioner in COOL operation in winter, activate trial operation
mode by following the instructions in the installation manual for the indoor unit.
The air conditioner draws a small amount of power in its standby mode. If the system is
not to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will
restore the original operation mode when the circuit breaker is opened again.
Test items
Symptoms
Indoor and outdoor units are installed securely.
Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain
hose extension are thermally insulated.
Water leakage
Draining line is properly installed.
Water leakage
System is properly earthed.
Electrical leakage
Only specified wires are used for all wiring, and all
wires are connected correctly.
No operation or burn damage
Indoor or outdoor unit’s air inlet or air outlet are
unobstructed.
Incomplete cooling/heating function
Stop valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives remote control
commands.
No operation
Pipes and wires are connected to the corresponding
terminal blocks/connection ports for the connected
unit. *
No heating
Temperature difference between inlet and outlet
About 8°C
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...