Check
SiSG121917E
179
Part 6 Service Diagnosis
90 class
To prevent electrical shock, use a multimeter to check that the voltage between FU2 and
DC_N2 is 50 V or less.
The surface of the test points (FU2, DC_N2) may be covered with the coating. Be sure to
make firm contact between the multimeter probes and the test points.
8.14 Power Module Check
Check No.22
Check to make sure that the voltage between (+) and (–) of the power module is approximately
0 V before checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the (+) or (–) terminal of the
power module and the U, V, or W terminal of the compressor with a multimeter. Evaluate the
measurement results referring to the following table.
FU2
DC_
N
2
(R21124)
M
u
ltimeter
(DC
v
oltage range)
FU2
DC_N2
Coating
PCB
Multimeter probe
(R21125)
Positive terminal (+) of
digital multimeter
Power module
(+)
UVW
Power module
(–)
UVW
Negative terminal (–) of
digital multimeter
UVW
Power module
(+)
UVW
Power module
(–)
Resistance is OK.
several k
~ several M
Resistance is NG.
0
or
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...