Troubleshooting for Outdoor Unit
SiSG121917E
139
Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
Check No.01
Refer to P.169
Check No.12
Refer to P.172
(R20401)
Caution
YES
NG
NO
NO
YES
YES
YES
NO
NO
YES
YES
NO
YES
NO
NO
∗
Discharge pipe thermistor
∗
Indoor or outdoor heat exchanger thermistor
∗
Room temperature thermistor
∗
Outdoor temperature thermistor
Check for refrigerant shortage.
Change for a specified amount of
fresh refrigerant.
Check No. 12
Electronic expansion valve
functioning?
Replace the thermistor(s)
in
position.
Open the stop valve.
Repair the pipe flare or
replace the union.
Check the pipes for
improper contact and
correct them as required.
Replace the cracked pipe.
Check the power transistor
harness for loosening.
Correct it as required. Also
replace the cracked pipe.
Replace the electronic
expansion valve.
Replace the defective
thermistor(s).
Completed.
Refrigerant shortage error
again?
Oil oozing at internal
piping?
Stop valve closed?
Compressor vibrating
too much?
Oil oozing at relay
pipe connections?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
OK
YES
NO
Replace the outdoor unit PCB
(main PCB).
Replace the compressor.
Completed.
Error again?
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...