MSP Duct Type Functions
SiSG121917E
65
Part 4 Functions and Control
If Float Switch is ON with Thermostat OFF in Cooling Operation
When the float switch turns OFF, the drain pump turns ON simultaneously.
If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code
A3
is displayed on the remote controller.
The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
If Float Switch Turns ON and OFF Continuously, or Float Switch Turns ON While
AF
Displayed
When the float switch turns OFF, the drain pump turns ON simultaneously.
Notes:
1. If the float switch continues to turn OFF and ON 5 times consecutively, it is judged as a drain
system error and the error code
AF
is displayed on the remote controller.
2. The drain pump continues to turn ON/OFF in accordance with the float switch ON/OFF even
after
AF
is displayed on the remote controller.
3. While the error code
AF
is displayed, if the float switch remains OFF even after the residual
operation of the drain pump has ended, the error code
A3
will be displayed on the remote
controller.
OFF
OFF
O
N
O
N
O
N
OFF
O
N
OFF
5 min. 5 sec.
(R24671)
Float s
w
itch
Error display
Thermostat
(r
u
nning)
Drain p
u
mp
A3
OFF
OFF
O
N
O
N
O
N
OFF
O
N
OFF
5 min.
5 min.
5 min.
5 min.
5 min.
5 min.
5 sec.
5 min.
(R24672)
1st
2nd
3rd
4th
5th
AF
A3
Float s
w
itch
Error display
Thermostat
(r
u
nning)
Drain p
u
mp
∗
1
∗
3
∗
2
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...