SiSG121917E
MSP Duct Type Functions
Part 4 Functions and Control
66
2.2 Thermostat Sensor in Wired Remote Controller
Outline
Temperature is controlled by both the thermostat sensor in wired remote controller and air
suction thermostat in the indoor unit. This is however limited to when the field setting for the
thermostat sensor in wired remote controller is set to Use.
Cooling
If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
wired remote controller near the position of the user when the suction temperature is near the
set temperature.
Assuming the set temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 30°C (A → F):
(This example also assumes there are several other air conditioners, and the suction
temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 23°C (A → C).
Wired remote controller thermostat sensor is used for temperatures from 23°C to 27°C (C → E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E → F).
Assuming suction temperature has changed from 30°C to 18°C (F → A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F → D).
Wired remote controller thermostat sensor is used for temperatures from 25°C to 21°C (D → B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B → A).
Set temperat
u
re
(Ts)
Range in
w
hich thermostat sensor
in remote controller can
b
e
u
sed
Range in
w
hich
b
ody
thermostat sensor can
b
e
u
sed
Differential
S
u
ction temperat
u
re (TH1)
TH1 = Ts - 1
TH1 = Ts + 1
TH1 = Ts + 3
TH1 = Ts - 3
A
B
C
D
E
F
(R17
8
55)
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...