Troubleshooting for Wall Mounted and LSP Duct Type Indoor Unit
Part 6 Service Diagnosis
122
Reference
Troubleshooting
Check No.04
Refer to P.171
(R21106)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Check the power supply voltage.
Correct the power supply.
Is the
voltage fluctuation
within ±10% from the
rated value?
NO
NO
NO
NO
NO
YES
YES
NO
YES
YES
YES
YES
Replace the fan motor or the
indoor unit PCB (control PCB).
Replace the fan motor.
Replace the indoor unit PCB
(control PCB).
Replace the fan motor.
Replace the capacitor.
(Replace the indoor unit PCB
(control PCB).)
Replace the fan motor.
Replace the indoor unit PCB
(control PCB).
∗
Measure the voltage
between the black and white
lead wires of the fan motor,
and check if the maximum
voltage reaches the rated
voltage.
Check No. 04
Check Hall IC
Is there an output?
Check the fan motor voltage.
V
oltage as rated?
∗
Start operation.
Does the fan rotate?
Turn off the power and rotate
the fan by hand.
Does the fan rotate
smoothly?
Turn on the power and check the
fan motor voltage. (immediately
after restart)
V
oltage as rated?
∗
Check the capacitor's continuity.
Is there continuity?
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...