4 Power Input Module
4.3
Front Panel and Connectors
The following
fi
gure shows the PIM front panel.
Fig. 13 8665 Smart Router Power Input Module
The input connector is located on the front side of the PIM. The -48 Vdc output voltage and signal
connector is located on the back side of the PIM.
4.4
Input Fault Detection and LEDS
On the PIM there is a voltage monitor for input voltage detection. If the input voltage after the
fuse is missing or too low, an alarm is forwarded to the CU on the LU1, and a LED indicates the
input voltage status.
LED Name
Color
States
Battery Voltage
GREEN
ON
when Input voltage is valid.
OFF
otherwise.
4.5
Cabling
The PIM can be used with normal copper power cables as screw terminals are used. The maximum
conductor cross section is 25 mm
2
(solid), 16 mm
2
(stranded) and 16 mm
2
(with ferrule). The
router can be wired with either single power cable pair or two pairs of cables if thinner cable is
preferred in the installation.
Also a grounding cable with the same or thicker cross-sectional area than the power cable must
be used with the 8665 Smart Router subrack with PIMs installed; that is, at least 16 mm
2
(approximately 5 AWG) or 25 mm
2
(approximately 3 AWG). For more details on power and
grounding cabling, please refer to
8600 Smart Routers Hardware Installation Guide
.
8600 Smart Routers
76.8670-40128B
8665 Smart Router FP7.0 Reference Manual
© 2015 Coriant.
46