20-17
Catalyst 6000 Family Software Configuration Guide—Releases 6.3 and 6.4
78-13315-02
Chapter 20 Administering the Switch
Displaying System Status Information for Technical Support
Displaying System Status Information for Technical Support
These sections describe how to display system status information for technical support:
•
Generating a System Status Report, page 20-18
•
Using System Dump Files, page 20-18
Table 20-3 Environmental Monitoring for Supervisor Engine and Switching Modules
Component
Alarm
Type
LED Indication
Action
Supervisor engine
temperature sensor exceeds
major threshold
1
1.
Temperature sensors monitor key supervisor engine components including daughter cards.
Major STATUS
2
LED red
3
2.
A STATUS LED is located on the supervisor engine front panel and all module front panels.
3.
The STATUS LED is red on the failed supervisor engine. If there is no redundant supervisor, the SYSTEM LED is red also.
syslog message and SNMP trap
generated.
If redundancy, system switches to
redundant supervisor engine and the
active supervisor engine shuts down.
If there is no redundancy and the
overtemperature condition is not
corrected, the system shuts down after
5 minutes.
Supervisor engine
temperature sensor exceeds
minor threshold
Minor
STATUS LED
orange
syslog message and SNMP trap
generated.
Monitor the condition.
Redundant supervisor engine
temperature sensor exceeds
major or minor threshold
Major
STATUS LED red
syslog message and SNMP trap
generated.
If major alarm and the overtemperature
condition is not corrected, the system
shuts down after 5 minutes.
Minor
STATUS LED
orange
If minor alarm, monitor the condition.
Switching module
temperature sensor exceeds
major threshold
Major STATUS LED red
syslog message and SNMP trap
generated.
Power down the module
4
.
4.
See the
“Power Management” section on page 20-11
for instructions.
Switching module
temperature sensor exceeds
minor threshold
Minor
STATUS LED
orange
syslog message and SNMP trap
generated.
Monitor the condition.