3-20
Cisco ONS 15200 Installation, Setup, and Test Manual
78-13765-01
Chapter 3 Installation
Note
Clean all optical connectors and use covers to protect them.
Caution
Static electricity can damage electro-optical equipment. While unpacking and handling
electro-optical modules, wear a grounding wrist strap to discharge the static buildup. Grounding
wrist straps are designed to prevent equipment damage caused by static electricity. Before making
the necessary interconnections, connect the grounding wrist strap.
Caution
Do not use the AC cord that can be ordered for the SCU in cable management devices such as wiring
ducts, plenums, or risers. For such applications, you must provide an approved AC power cord. At
minimum, the AC power cord must meet all National Electrical Code (NFPA 70, National Electrical
Code, 2000 Edition) and all local building code requirements. This applies to Central Offices and
other buildings.
The ONS 15201 SCU, shown in
, is designed to be installed at ONS 15200 system client
sites.
Procedure: Mount the ONS 15201 SCU in an Equipment Rack
Step 1
Align four M6 cage nuts in the equipment rack with the mounting holes on the front of the SCU.
Step 2
Align the SCU with the equipment rack and cage nuts.
Step 3
Insert the SCU into the equipment rack.
Step 4
Connect the SCU to the equipment rack with four M6 screws.
Содержание ONS 15200 Series
Страница 26: ...2 6 Cisco ONS 15200 Installation Setup and Test Manual 78 13765 01 Chapter 2 Pre Installation Procedures ...
Страница 86: ...3 60 Cisco ONS 15200 Installation Setup and Test Manual 78 13765 01 Chapter 3 Installation ...
Страница 108: ...4 22 Cisco ONS 15200 Installation Setup and Test Manual 78 13765 01 Chapter 4 Turn Up and Test ...
Страница 130: ...B 12 Cisco ONS 15200 Installation Setup and Test Manual 78 13765 01 Appendix B Acceptance Test Plan ...
Страница 136: ...Index IN 6 Cisco ONS 15200 Installation Setup and Test Manual 78 13765 01 ...