Chapter 2 Installing the Cisco MDS 9500 Series
System Grounding
Table 2-4
Grounding Best Practices
Environment
Electromagnetic Noise Severity
Level
Grounding Recommendations
Commercial building is
subjected to direct lightning
strikes.
For example, some places in the
United States, such as Florida,
are subject to more lightning
strikes than other areas.
High
All lightning protection devices
must be installed in strict
accordance with manufacturer
recommendations. Conductors
carrying lightning current
should be spaced away from
power and data lines in
accordance with applicable
recommendations and codes.
Appropriate grounding practices
must be closely followed.
Commercial building is located
in an area where lightning
storms frequently occur but is
not subject to direct lightning
strikes.
High
Appropriate grounding practices
must be closely followed.
Commercial building contains a
mix of information technology
equipment and industrial
equipment, such as welding.
Medium to high
Appropriate grounding practices
must be closely followed.
Existing commercial building is
not subject to natural
environmental noise or
man-made industrial noise. This
building contains a standard
office environment. This
installation has a history of
malfunction due to
electromagnetic noise.
Medium
Appropriate grounding practices
must be closely followed.
Determine source and cause of
noise if possible, and mitigate as
closely as possible at the noise
source or reduce coupling from
the noise source to the victim
equipment.
New commercial building is not
subject to natural environmental
noise or man-made industrial
noise. This building contains a
standard office environment.
Low
Appropriate grounding practices
should be followed as closely as
possible. Electromagnetic noise
problems are not anticipated, but
installing a best practice
grounding system in a new
building is often the least
expensive route and the best way
to plan for the future.
Existing commercial building is
not subject to natural
environmental noise or
man-made industrial noise. This
building contains a standard
office environment.
Low
Appropriate grounding practices
should be followed as much as
possible. Electromagnetic noise
problems are not anticipated, but
installing a best practice
grounding system is always
recommended.