S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m .
D-16
Cisco MDS 9500 Series Hardware Installation Guide
OL-17467-02
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9506 Director
Component Power Requirements and Heat Dissipation for the Cisco MDS 9506
Director
When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power
and heat associated with a Cisco MDS 9506 Director varies depending upon the following:
•
Power supply type
•
Switching module type and number of switching modules installed
•
Average switching traffic levels
Table D-16
and
Table D-17
list the AC and DC power requirements and heat dissipation for the
components of the Cisco MDS 9506 Director.
Note
Unless noted otherwise, the information listed in
Table D-16
and
Table D-17
is based on worst-case
conditions. Typical numbers are approximately 30 percent below the numbers listed here.
Table D-16
Power Requirements and Heat Dissipation for the 1900-W AC Power Supply
Module Type/
Product Number
NX-OS
Release
SAN-OS
Release
Power
Required
(watts)
Heat
Dissipation
(BTU/hr)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)
Cisco MDS 9506 chassis with fan
module
DS-C9506
3.x
126
538
1.75
1.31
0.88
0.66
2.x and
1.x
126
538
1.75
1.32
0.88
0.66
Supervisor/fabric 1
DS-X9530-SF1
3.x
210
897
2.92
2.19
1.46
1.09
2.x and
1.x
220
940
3.05
2.29
1.53
1.15
Supervisor-2, DS-X9530-SF2-K9
3.x
126
538
1.75
1.31
0.88
0.66
48-port 4-Gbps switching module,
DS-X9148
3.x
185
790
2.57
1.93
1.28
0.96
2.x and
1.x
—
—
—
—
—
—
24-port 4-Gbps switching module,
DS-X9124
3.x
147
628
2.04
1.53
1.02
0.77
2.x and
1.x
—
—
—
—
—
—
12-port 4-Gbps switching module,
DS-X9112
3.x
132
564
1.83
1.38
0.92
0.69
2.x and
1.x
—
—
—
—
—
—
4-Port 10-Gbps switching module,
DS-X9704
3.x
172
734
2.39
1.79
1.19
0.90
2.x and
1.x
—
—
—
—
—
—
32-port 1-Gbps/2-Gbps Fibre
Channel module
DS-X9032
3.x
191
816
2.65
1.99
1.33
0.99
2.x and
1.x
200
855
2.78
2.08
1.39
1.04