S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m .
D-8
Cisco MDS 9500 Series Hardware Installation Guide
OL-17467-02
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9513 Director
AC Power Consumption for the Cisco MDS 9513 Director
Table D-10
shows the typical AC power consumption for a Cisco MDS 9513 Director.
Table D-9
Requirements and Heat Dissipation for 6000-W AC Power Supplies
Module Type/
Product Number
NX-OS
Release
SAN-OS
Release
Power
Required
(watts)
Heat
Dissipation
(BTU/hr)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)
Fan tray 1 (front panel),
DS-13SLT-FAN-F
3.x
248
1059
3.44
2.58
1.72
1.29
Fan tray 2 (rear panel),
DS-13SLT-FAN-R
3.x
70
299
0.97
0.73
0.49
0.36
Cisco MDS 9513 chassis,
DS-C9513, with front
(DS-13SLT-FAN-F) and rear
(DS-13SLT-FAN-R) fan trays
3.x
318
1358
4.41
3.31
2.21
1.65
Supervisor-2, DS-X9530-SF2-K9
3.x
126
538
1.75
1.31
0.88
0.66
48-port 4-Gbps switching module,
DS-X9148
3.x
185
790
2.57
1.93
1.28
0.96
24-port 4-Gbps switching module,
DS-X9124
3.x
147
628
2.04
1.53
1.02
0.77
12-port 4-Gbps switching module,
DS-X9112
3.x
132
564
1.83
1.38
0.92
0.69
4-Port 10-Gbps switching module,
DS-X9704
3.x
172
734
2.39
1.79
1.19
0.90
18/4 Multiservice module,
DS-X9304-18K9
3.2.(1)
200
855
2.78
2.08
1.39
1.04
Crossbar module, DS-13SLT-FAB1,
DS-13SLT-FAB2
3.x
63
269
0.88
0.66
0.44
0.33
48-port 8-Gbps switching module,
DS-X9248-96K9
4.x
298
1273
4.14
3.11
2.07
1.55
24-port 8-Gbps switching module,
DS-X9224-96K
4.x
273
1163
3.79
2.84
1.90
1.42
4/44-port 8-Gbps Host-Optimized
switching module,
DS-X9248-48K9
4.x
214
915
2.98
2.23
1.49
1.12