S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m .
D-7
Cisco MDS 9500 Series Hardware Installation Guide
OL-17467-02
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9513 Director
•
Two AC power connection @ 220 VAC = 6000 W output
If a 110 VAC input is chosen, a 110-VAC power cord (CAB-7513AC=) must be ordered separately.
Note
Power output does not include the power used by the individual modules used in the chassis.
Table D-8
lists the specifications for the Cisco MDS 9513 power supplies.
Component Power Requirements and Heat Dissipation for the Cisco MDS 9513
Director
Consider heat dissipation when sizing the air-conditioning requirements for an installation. The power
and heat associated with a Cisco MDS 9513 Director varies based upon the following considerations:
•
Power supply type
•
Switching module type and number of switching modules installed
•
Average switching traffic levels
Table D-9
lists the power requirements and heat dissipation for the components of the Cisco MDS 9513
Director.
Note
Unless noted otherwise, the data listed in
Table D-9
is based on worst-case conditions. Typical numbers
are approximately 30 percent below the numbers listed here.
Table D-8
Specifications for Cisco MDS 9513 Power Supplies
Description
Specification
6000-W AC Power Supply
Type
Autoranging input with power factor corrector.
Voltage
100 to 240 VAC (±10%).
Current rating
16 A maximum at 100 to 120 VAC and 2900-W output.
16 A maximum at 200 to 240 VAC and 6000-W output.
Frequency
50 to 60 Hz (nominal) (±3 Hz for full range).
Output capacity
One AC power connection @110 VAC = No output
Two AC power connection @110 VAC = 2900 W output
One AC power connection @ 220 VAC = 2900 W output
One AC power connection @110 VAC and one AC power connection
@ 220 VAC = 2900 W output
Two AC power connection @ 220 VAC = 6000 W output
Output voltage at 110/120 3.3 V at 10 A, 50 V at 57 A
Output voltage at 200/240 3.3 V at 10A, 50 V at 119 A