S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m .
D-12
Cisco MDS 9500 Series Hardware Installation Guide
OL-17467-02
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9509 Director
16-port 1-Gbps/2-Gbps Fibre
Channel module,
DS-X9016
3.x
210
897
2.92
2.19
1.46
1.09
2.x and
1.x
220
940
3.05
2.29
1.53
1.15
18/4 Multiservice module,
DS-X9304-18K9
3.2.(1)
200
855
2.78
2.08
1.39
1.04
MPS-14/2 module DS-X9302-14K9
3.x
200
854
2.78
2.08
1.39
1.04
2.x and
1.x
227
970
3.15
2.37
1.57
1.19
8-port IPS module
DS-X9308-SMIP
3.x
200
854
2.78
2.08
1.39
1.04
2.x and
1.x
220
940
3.05
2.29
1.53
1.15
4-port IPS module
DS-X9304-SMIP
3.x
160
683
2.22
1.67
1.11
0.83
2.x and
1.x
185
789
2.57
1.93
1.28
0.96
32-port SSM
DS-X9032-SSM
3.x
281
1200
3.90
2.93
1.95
1.46
2.x and
1.x
295
1260
4.10
3.07
2.05
1.54
32-port ASM
DS-X9032-SMV
3.x
281
1200
3.90
2.93
1.95
1.46
2.x and
1.x
295
1260
4.10
3.07
2.05
1.54
CSM
DS-X9560-SMC
3.x
200
854
2.78
2.08
1.39
1.04
2.x and
1.x
210
919
2.99
2.19
1.50
1.12
48-port 8-Gbps switching module,
DS-X9248-96K9
4.x
298
1273
4.14
3.11
2.07
1.55
24-port 8-Gbps switching module,
DS-X9224-96K
4.x
273
1163
3.79
2.84
1.90
1.42
4/44-port 8-Gbps Host-Optimized
switching module,
DS-X9248-48K9
4.x
214
915
2.98
2.23
1.49
1.12
Table D-12
Requirements and Heat Dissipation for 2500-, 3000-, and 4000-W AC Power Supplies (continued)
Module Type/
Product Number
NX-OS
Release
SAN-OS
Release
Power
Required
(watts)
Heat
Dissipation
(BTU/hr)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)