54-12
Cisco 7600 Series Router Cisco IOS Software Configuration Guide, Release 12.2SX
OL-4266-08
Chapter 54 Power Management and Environmental Monitoring
Understanding How Environmental Monitoring Works
When the system has an alarm (major or minor), that indicates an overtemperature condition, the alarm
is not canceled nor is any action taken (such as module reset or shutdown) for 5 minutes. If the
temperature falls 5°C (41°F) below the alarm threshold during this period, the alarm is canceled.
Table 54-2
lists the environmental indicators for the supervisor engine and switching modules.
Note
Refer to the
Cisco 7600 Series Router Module Installation Guide
for additional information on LEDs,
including the supervisor engine SYSTEM LED.
Tip
For additional information (including configuration examples and troubleshooting information), see the
documents listed on this page:
http://www.cisco.com/en/US/products/hw/routers/ps368/tsd_products_support_series_home.html
Table 54-2 Environmental Monitoring for Supervisor Engine and Switching Modules
Component
Alarm
Type
LED Indication
Action
Supervisor engine temperature sensor
exceeds major threshold
1
1.
Temperature sensors monitor key supervisor engine components including daughter cards.
Major STATUS
2
LED red
3
2.
A STATUS LED is located on the supervisor engine front panel and all module front panels.
3.
The STATUS LED is red on the failed supervisor engine. If there is no redundant supervisor, the SYSTEM LED is red also.
Generates syslog message and an SNMP trap.
If there is a redundancy situation, the system
switches to a redundant supervisor engine and the
active supervisor engine shuts down.
If there is no redundancy situation and the
overtemperature condition is not corrected, the
system shuts down after 5 minutes.
Supervisor engine temperature sensor
exceeds minor threshold
Minor
STATUS LED
orange
Generates syslog message and an SNMP trap.
Monitors the condition.
Redundant supervisor engine
temperature sensor exceeds major or
minor threshold
Major
Minor
STATUS LED red
STATUS LED
orange
Generates syslog message and an SNMP trap.
If a major alarm is generated and the
overtemperature condition is not corrected, the
system shuts down after 5 minutes.
Monitors the condition if a minor alarm is generated.
Switching module temperature sensor
exceeds major threshold
Major STATUS LED red
Generates syslog message and SNMP.
Powers down the module
4
.
4.
See the
“Understanding How Power Management Works” section on page 54-1
for instructions.
Switching module temperature sensor
exceeds minor threshold
Minor
STATUS LED
orange
Generates syslog message and an SNMP trap.
Monitors the condition.