3) Zone1, and DHW tank
He ating/Cooling:
In the case of water temp control, Par4100=0, the HP unit operates in order for S1 to reach the set point
(Fixed or Climatic curve)
In the case of room temp control, Par4100=1, the HP unit can be turned ON/OFF by T1 and the set point of
Remote controller.
DH W tank:
The HP unit operates with maximum water temperature in Heating (60°C) in order for S2 to reach the DHW
set point.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
41
00
T he HP unit turns ON/OFF based on
0=Room set point
1=Water set point
1
0
1
-
S1
S2
M
HP unit
DHW tank
T1
Zone1
95