8.2.2 DHW Electric heater only
In this configuration, the DHW tank will only be heated using the DHW Electric heater.
If the Par3102=2 (Heater only), the heat pump produces hot or cool water for the system and the hot water will be
heated by the electrical heater only.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
31
02
T ype of configuration to heat the DHW
0=Heat pump + Heater
1=Heat pump only
2=Heater only
1
0
2
-
I
31
11
DHW Comfort set temperature
50.0
40.0
60.0
0.5°C
I
31
12
DHW Economy set temperature
40.0
30.0
50.0
0.5°C
I
31
13
DHW set point hysteresis
3.0
0.5
10.0
0.5°C
I
31
14
DHW Over boost set point
60.0
50.0
90.0
0.5°C
I
31
15
DHW Over boost set point hysteresis
5.0
0.5
10.0
0.5°C
(3.0°C)
DHW hysteresis
DHW tank
temperature
DHW Electric heater
ON
OFF
DHW set point
Comfort
Economy
Over boost
(50.0°C)
(40.0°C)
(60.0°C)
103
8. Domestic Hot Water Production
Содержание AEYC-0639U-CH
Страница 156: ...20810030 M ...