Water temperature set points of Heating/Cooling
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
21
24
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone1
25.0
0.0
50.0
0.5°C
I
21
25
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone1
35.0
0.0
50.0
0.5°C
I
21
30
C ooling Zone2, enable Outgoing water set point
0=Fixed set point
1=Climatic Curve Enabled
0
0
1
-
I
21
31
Cooling Zone2, Fixed Outgoing water set point in
Cooling
7.0
7.0
23.0
0.5°C
I
21
32
Max. Outgoing water temperature in Cooling mode
(Tm1) Zone2
20.0
7.0
23.0
0.5°C
I
21
33
Min. Outgoing water temperature in Cooling mode
(Tm2) Zone2
18.0
7.0
23.0
0.5°C
I
21
34
Min. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te1) Zone2
25.0
0.0
50.0
0.5°C
I
21
35
Max. Outdoor air temperature corresponding to max.
Outgoing water temperature (Te2) Zone2
35.0
0.0
50.0
0.5°C
I
21
41
Hysteresis of water set point in Heating and DHW
8.0
0.5
10.0
0.5°C
I
21
42
Hysteresis of water set point in Cooling
8.0
0.5
10.0
0.5°C
I
21
51
Low tariff deferential water set point for Heating
5.0
0.0
60.0
0.5°C
I
21
52
Low tariff deferential water set point for Cooling
5.0
0.0
60.0
0.5°C
I
21
61
Buffer tank set point for Heating
45.0
23.0
60.0
0.5°C
I
21
62
Buffer tank set point for Cooling
7.0
7.0
23.0
0.5°C
DHW (Domestic Hot Water)
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
31
01
DHW production priority setting
0=DHW is unavailable
1= DHW is available, and priority DHW over space
Heating
2= DHW is available, and priority space Heating over
DHW
0
0
2
-
I
31
02
T ype of configuration to heat the DHW
0=Heat pump + Heater
1=Heat pump only
2=Heater only
1
0
2
-
I
31
11
DHW Comfort set temperature
50.0
40.0
60.0
0.5°C
I
31
12
DHW Economy set temperature
40.0
30.0
50.0
0.5°C
I
31
13
DHW set point hysteresis
3.0
0.5
10.0
0.5°C
I
31
14
DHW Over boost mode set point
60.0
50.0
90.0
0.5°C
I
31
15
DHW Over boost mode set point hysteresis
5.0
0.5
10.0
0.5°C
I
31
21
Max. time for DHW request
60
0
900
1min
I
31
22
Min. time for space Heating/Cooling
15
0
900
1min
I
31
32
C onditions to be available DHW heaters
0=always enabled
1=depends on Outdoor air temperature
1
0
1
-
I
31
33
Outdoor air temperature to enable DHW heaters
-5.0
-20.0
20.0
0.5°C
I
31
34
Outdoor air temperature hysteresis to disable DHW
heaters
5.0
0.5
10.0
0.5°C
I
31
40
A nti-legionella function
0=disable
1=enable
0
0
1
-
I
31
41
A nti-legionella operation day of week
0=Mon, 1=Tue, 2=Wed, 3=Thu, 4=Fri, 5=Sat, 6=Sun
0
0
6
-
I
31
42
Start time of the day at which the DHW should be
heated for Anti-legionella
1:00
0:00
23:00
1:00
132
9. Parameters List