8.4.2 EHS in Supplementary mode
Once space heating is enabled, the EHS will be activated according to the water temperature as shown in the
following graph.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
47
00
E HS type of function
0=disable
1=Replacement mode
2=Supplementary mode
0
0
2
-
Par4600 and Par4700
are synchronize
Par4600=1, 2, 3
→ Par=4700=0
Par4700=1, 2
→ Par4600=0
I
47
06
EHS activation delay time
5
0
900
1min
I
47
07
Integration time for starting EHS
600
0
900
1°C×sec
8. Domestic Hot Water Production
time
EHS ON
OFF
water temperature
hysteresis
HP control set point
Compressor ON
OFF
EHS
activation
delay
(5min)
Integration time for starting EHS
(600°C×sec)
Real water temperature
The “HP control set point” is equal to the value set for Fixed set point control, or by the value determined by the
Climatic curve.