3. Installation
Do not use the heat pump to treat industrial process water, swimming pool water or domestic water.
Set-up an intermediate heat exchanger for all the above cases.
CAUTION
• The quantity of water in the system must not be less than 30 litres
• If the quantity of water in the system is higher than 160 litres, use an additional Buffer tank
3.5 Water circuit connection
Buffer tank
Mani fold
Outlet
Inlet
DHW tank
M
Space Heating
Dehumidifier
M
Fan convector
Radiant panel
F
P
T
P
T
1
2
1
2
3
8
9
8
9
6
5
7
4
11
13
14
12
10
15
19
17
18
16
16
19
20
Shut-off valve
Vibration damper joint
Air bleed valve
Fill/drain valve
Water line filter
Flow switch
Expansion vessel
Pressure gauge
Thermometer
Backup heater*
DHW 3way valve
DHW tank temperature probe
DHW Electric heater
EHS*
Buffer tank temperature probe
Additional water pump
Mixing valve
Mix water temperature probe
Remote controller
Humidity sensor
* Backup heater and EHS
cannot be used at same time.