Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
47
00
E HS type of function
0=disable
1=Replacement mode
2=Supplementary mode
0
0
2
-
Par4600 and Par4700
are synchronize
Par4600=1, 2, 3
→ Par=4700=0
Par4700=1, 2
→ Par4600=0
I
47
01
C onditions to be available EHS
0=always enabled
1=depends on Outdoor air temperature
1
0
1
-
I
47
02
Outdoor air temperature to enable EHS and disable
compressor
-5.0
-20.0
20.0
0.5°C
I
47
03
Outdoor air temperature hysteresis to disable EHS and
enable compressor
5.0
0.5
10.0
0.5°C
I
51
41
Terminal 41-42 : EHS (External heat source for space
heating)
0=disable
1=enable
0
0
1
-
When the switching of the HP unit ON/OFF is based on water temperature set point, the EHS will be activated
according to the water temperature set point based on “Fixed set point” or based on “Climatic curve”.
When the switching of the HP unit ON/OFF is based on Room air temperature, the EHS will be activated according
to the Room air temperature set point based on “HP unit control”.
120
8. Domestic Hot Water Production