111
Note1: If “Frost protection on Room air temperature” is activated, the top priority is the set point of Frost protection
(Par4303=35°C) than that of Emergency mode (Par4601=50°C).
Note2: The Backup heater will be available for the System during “Min. time for space Heating/Cooling” after the
“Max. time for DHW request” or if it reaches the DHW water set point.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
46
00
B ackup heater type of function
0=disable
1=Replacement mode
2=Emergency mode
3=Supplementary mode
0
0
3
-
Par4600 and Par4700
are synchronized
Par4600=1, 2, 3
→ Par=4700=0
Par4700=1, 2
→ Par4600=0
I
46
01
Manual water set point
50.0
40.0
60.0
0.5°C
I
46
02
Manual water temperature hysteresis
5.0
0.5
10.0
0.5°C
I
31
21
Max. time for DHW request
60
0
900
1min
I
31
22
Min. time for space Heating/Cooling
15
0
900
1min
8. Domestic Hot Water Production