Maximum Room humidity compensation
The Outgoing water set point, calculated based on the Climatic curve, can be compensated according to the
maximum relative humidity in the room to prevent and to avoid possible formation of condensate in the floor in
case of floor cooling system.
If the humidity measured by the humidity sensor exceeds the value specified by Par4410 and 4411, the Outgoing
water set point increases until the maximum Outgoing temperature has been reached.
The maximum Outgoing temperature is the set point calculated according to the compensation curve in the
Cooling mode + Hysteresis value set by the dedicated parameter.
Note: If the HP unit is connected directly to the system, without Buffer tank, the maximum Room humidity
compensation has effect on the Outgoing water temperature from the HP unit. If the HP unit is connected to
the Buffer tank and the low temperature Zone with a 3way mixing valve is enabled, the maximum Room
humidity compensation has effect on the Outgoing water temperature from mixing valve.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
44
10
C ompensation for room humidity
0=disable
1=enable
1
0
1
-
I
44
11
Room relative humidity value to start increasing
Outgoing water temperature set point
55
0
100
1%
I
44
12
Maximum Outgoing temperature hysteresis
corresponding to 100% relative humidity
10.0
0.5
20.0
0.5°C
(55%RH)
100%
Room humidity(RH%)
hysteresis
Hysteresis(°C)
Outgoing water set point
Hysteresis value
(10.0°C)
91