The Humidity Sensor connected in the Terminal 17-18. The controller receives the relative humidity signal in the
form of voltage signals (DC0~10 V).
The respective room humidity is calculated via the linear characteristic which is defined by 2 fixed points (voltage
value1 / function value1 and voltage value2 / function value2).
Note: Alarm control logic
PCB(Controller) displays error code L5 (Sensor Humidity failure), when the detected voltage of Humidity
sensor (Terminal 17-18) is below DC0.15V or above DC9.8V.
Considering 2% of deviation for PCB circuit, the alarm may be displayed if the humidity is 96% or higher
(DC9.6V or higher).
The controller compares room humidity (detected with humidity sensor) with the humidity set point (Par 4401,
4402) and switches the external dehumidifier connected to the Terminal 45-N.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
44
01
Room relative humidity value
60
0
100
1%
I
44
02
Hysteresis value
10
1
100
1%
I
44
03
Humidity sensor property, Voltage value1
0.0
0.0
10.0
0.1V
I
44
04
Humidity sensor property, Voltage value2
10.0
0.0
10.0
0.1V
I
44
05
Humidity sensor property, Function value1
0
0
100
1%
I
44
06
Humidity sensor property, Function value2
100
0
100
1%
(10%)
Humidity set point
(60%)
hysteresis
Room humidity(%)
Dehumidifier ON
OFF
(10.0V)
Voltage value2
(5.5V)
Detected value
(0.0V)
Voltage value1
Voltage(V)
Room humidity(%)
Function value2(100%)
Calculated
Room humidity(55%)
Function value1(0%)
90
7. Unit Management