8.2.1 Heat pump only
The HP unit is activated to produce DHW, if the DHW tank temperature falls below the value set for parameter
“Economy DHW set point – DHW hysteresis” or “Comfort DHW set point – DHW hysteresis”.
HP unit stops DHW production:
A) When the DHW tank temperature reached to DHW set point.
B) When Outgoing water temperature reaches to the maximum set temperature, according to the operating
limits of HP unit.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
31
02
T ype of configuration to heat the DHW
0=Heat pump + Heater
1=Heat pump only
2=Heater only
1
0
2
-
I
31
11
DHW Comfort set temperature
50.0
40.0
60.0
0.5°C
I
31
12
DHW Economy set temperature
40.0
30.0
50.0
0.5°C
I
31
13
DHW set point hysteresis
3.0
0.5
10.0
0.5°C
I
31
14
DHW Over boost set point
60.0
50.0
90.0
0.5°C
I
31
15
DHW Over boost set point hysteresis
5.0
0.5
10.0
0.5°C
(3.0°C)
DHW hysteresis
DHW tank
temperature
Compressor ON
OFF
DHW set point
Comfort
Economy
Over boost
(50.0°C)
(40.0°C)
(60.0°C)
101
8. Domestic Hot Water Production